Exhaust Fan Size Chart: CFM by Room (2026)
A bathroom up to 100 sq ft with an 8 ft ceiling needs 1 CFM of exhaust per square foot of floor, and never less than 50 CFM. The charts below cover taller ceilings, larger bathrooms, kitchens and whole-house ventilation, with the arithmetic shown.
Exhaust fans are rated in cubic feet per minute (CFM), the volume of air they move out of the house. ASHRAE Standard 62.2 sets the minimums most building codes follow, and the Home Ventilating Institute (HVI) publishes the room-sizing rules most manufacturers use. Find your room in the charts, use the next row up if it falls between two, and round up to the nearest fan setting. For what each kind of fan is for and how to choose one, start with our home ventilation and exhaust fans guide.
Bathrooms up to 100 sq ft
HVI sizes a bathroom of up to 100 sq ft at 1 CFM per square foot of floor, counting the shower and tub area, and ASHRAE 62.2 sets 50 CFM as the minimum for a bathroom fan that runs when the room is in use. HVI’s rule assumes an 8 ft ceiling. For taller ceilings the chart scales by volume: multiply by the ceiling height divided by 8, then round up. That step is ours, not HVI’s.
| Floor area | 8 ft ceiling | 9 ft ceiling | 10 ft ceiling |
|---|---|---|---|
| 40 sq ft or less | 50 CFM | 50 CFM | 50 CFM |
| 50 sq ft | 50 CFM | 57 CFM | 63 CFM |
| 60 sq ft | 60 CFM | 68 CFM | 75 CFM |
| 70 sq ft | 70 CFM | 79 CFM | 88 CFM |
| 80 sq ft | 80 CFM | 90 CFM | 100 CFM |
| 90 sq ft | 90 CFM | 102 CFM | 113 CFM |
| 100 sq ft | 100 CFM | 113 CFM | 125 CFM |
A 5 by 8 ft hall bath is 40 sq ft, so ASHRAE 62.2’s 50 CFM minimum governs (HVI’s floor-area rule alone gives 40). An 8 by 10 ft bath under a 9 ft ceiling needs 90 CFM, which rules out a fan whose top setting is 80.
Bathrooms over 100 sq ft
Above 100 sq ft, HVI stops counting floor area and counts fixtures instead: 50 CFM for each toilet, shower and tub, and 100 CFM for a jetted tub. HVI’s own example is a 20 by 12 ft bathroom with a tub, a separate shower and an enclosed toilet, which comes to 150 CFM.
| Fixtures (bathroom over 100 sq ft) | Total exhaust |
|---|---|
| Toilet and a shower or tub | 100 CFM |
| Toilet, tub and separate shower | 150 CFM |
| Toilet and jetted tub | 150 CFM |
| Toilet, jetted tub and separate shower | 200 CFM |
HVI allows the total to come from one fan near the center of the room or from separate fans over each fixture. An enclosed toilet room needs its own fan or an operable window, so if yours has neither, give it a 50 CFM fan and size the main fan for the remaining fixtures.
Kitchens
ASHRAE 62.2 gives two ways to meet the kitchen requirement. A vented range hood used while cooking needs at least 100 CFM. Any other kitchen fan used while cooking, such as a downdraft unit, needs 300 CFM or five air changes an hour of the kitchen’s volume. A fan that runs continuously needs five air changes an hour; the chart works that out as length times width times ceiling height, times 5, divided by 60.
| Kitchen size | Volume | Continuous exhaust (5 air changes an hour) |
|---|---|---|
| 10 by 10 ft, 8 ft ceiling | 800 cu ft | 67 CFM |
| 10 by 12 ft, 8 ft ceiling | 960 cu ft | 80 CFM |
| 12 by 15 ft, 8 ft ceiling | 1,440 cu ft | 120 CFM |
| 12 by 15 ft, 9 ft ceiling | 1,620 cu ft | 135 CFM |
| 15 by 20 ft, 9 ft ceiling | 2,700 cu ft | 225 CFM |
A recirculating hood filters grease and returns the air to the kitchen, so it does not meet either requirement.
Whole-House Ventilation
Spot fans clear one room while it is in use. ASHRAE 62.2 also sets a continuous outdoor-air rate for the whole home: 0.03 CFM per square foot of floor plus 7.5 CFM per occupant, with occupants counted as bedrooms plus one. The chart rounds the total up to a whole CFM. California’s energy code uses the same equation. A bathroom fan running continuously can count toward it.
| Home | Floor (0.03 x sq ft) | Occupants (7.5 x bedrooms + 1) | Continuous rate |
|---|---|---|---|
| 800 sq ft, 1 bedroom | 24 CFM | 15 CFM | 39 CFM |
| 1,000 sq ft, 2 bedrooms | 30 CFM | 22.5 CFM | 53 CFM |
| 1,500 sq ft, 3 bedrooms | 45 CFM | 30 CFM | 75 CFM |
| 2,000 sq ft, 3 bedrooms | 60 CFM | 30 CFM | 90 CFM |
| 2,500 sq ft, 4 bedrooms | 75 CFM | 37.5 CFM | 113 CFM |
| 3,000 sq ft, 4 bedrooms | 90 CFM | 37.5 CFM | 128 CFM |
These are totals before any allowance for air leaking in through the building. Where the local code allows it, a blower-door test that measures that leakage can lower the rate a fan must supply, so check with your building department or an energy rater before you size a fan to the full figure.
How Duct Length Changes the Fan You Need
A fan’s box rating is measured at 0.1 inch of static pressure, roughly a short, straight duct. Every foot of duct and every bend adds resistance, and the fan delivers less air as resistance rises. The prescriptive duct table in ASHRAE 62.2 (Table 5.3) rates fans at 0.25 inch instead. For an 80 CFM fan at that pressure, the table allows 3 feet of 4-inch flexible duct, 35 feet of 4-inch smooth metal duct or 70 feet of 5-inch flexible duct, for a straight run; it deducts 15 feet for each elbow, so a 4-inch flexible duct with a bend is ruled out at that size.
Size to the Delivered Airflow
On a long or bent duct run, pick a fan by its airflow at 0.25 inch, which some manufacturers and the ENERGY STAR product finder list alongside the box rating. Smooth or larger duct, or a fan with a 6-inch outlet, keeps more of that airflow.
Fans Matched to Each Size
These are the fans from our best bathroom exhaust fans guide, where each one is scored on delivered airflow, noise, efficiency, controls and value.
| Airflow you need | Fan | Settings | Price | Link |
|---|---|---|---|---|
| 50 to 110 CFM, ceiling with room for a 7-3/8 in housing | Panasonic FV-0511VQ1 | 50, 80 or 110 CFM | ~$153 | FV-0511VQ1 on Amazon (~$153) |
| 110 to 150 CFM | Panasonic FV-1115VQ1 | 110, 130 or 150 CFM | ~$208 | FV-1115VQ1 on Amazon (~$208) |
| 50 to 100 CFM, shallow ceiling or wall | Panasonic FV-0510VS1 | 50, 80 or 100 CFM | ~$91 | FV-0510VS1 on Amazon (~$91) |
| Up to 80 CFM in a room up to 75 sq ft, installed from below | Broan Flex AE80K | 80 CFM | ~$89 | AE80K at Sylvane (~$89) |
Frequently Asked Questions
What size exhaust fan do I need for a 100 sq ft bathroom?
100 CFM under an 8 ft ceiling. Scaled by volume, a 9 ft ceiling needs 113 CFM and a 10 ft ceiling 125 CFM, both above a fan whose top setting is 110 CFM.
How do I convert CFM to air changes per hour?
Multiply the CFM by 60 and divide by the room’s volume in cubic feet. An 80 CFM fan in an 8 by 10 ft bathroom with an 8 ft ceiling, 640 cu ft, gives 7.5 air changes an hour, which is what HVI’s square-foot rule works out to under an 8 ft ceiling.
Does a range hood need more than 100 CFM?
100 CFM is the ASHRAE 62.2 minimum for a vented hood, and many hoods are sold well above it. Under the International Residential Code, a hood capable of more than 400 CFM needs a makeup air supply when the home has a natural-draft gas, oil or wood-burning appliance inside the living space. Older code editions and some local codes require it regardless, so check with your building department before buying a very large hood.
Can a fan be bigger than the chart says?
A modest step up makes sense for a long duct run. A fan far above the room’s need wastes heated or cooled air, and in a home with a natural-draft furnace or water heater, ASHRAE 62.2 limits large exhaust flows; our ventilation guide covers that limit.